Eaton 9395 UPS family

Power Xpert 9395C UPS

The Eaton Power Xpert 9395C UPS has reached end-of-life status. Eaton will continue to provide services and replacement parts for the 9395C. If you’re looking for a new UPS, the Eaton 9395P and 9395XC are the replacement UPS offerings.

Power Xpert 9395P high-performance UPS

The Eaton 9395P offers up to 20% more power than the original Power Xpert 9395, all within the same footprint. The 9395P’s three-level converter topology operates components at less than half the stress of a conventional converter, which reduces energy losses and allows for higher power efficiency.

9395XC UPS

Designed to anticipate the growing needs of data centres for large power capacity, the 9395XC has the smallest footprint with the highest power density on the market and delivers reliable, flexible power protection.
Specifications

Power Xpert 9395C UPS technical specifications

UPS rating

1.0 power factor for 1000kVA/1000kW and 1100kVA/1100kW

0.91 power factor for 1100 kVA/1000kW only

kW/kVA 1,000 / 1,000
1,000 / 1,100
1,100 / 1,100
   
General characteristics  
Efficiency 

99% in Energy Saver System (ESS)

(up to 97% efficiency (480V) in double-conversion)

Parallel capability 

4 UPS units maximum for distributed bypass and

8 UPS units maximum with SBM

Audible noise  78dBA @ 1 metre
Altitude (max) 

1000 metres at 40°C (104°F) for 1000/1000

1000 metres at 40°C (104°F) for 1000/1100

1000 metres at 35°C (95°F) for 1100/1100

Control panel (LCD) Colour touchscreen interface
Battery start-up Standard
Frequency conversion Standard
Multi-language Standard
Building alarm inputs 5 (galvanic isolated)
   
Input characteristics  
Voltage 480V 3Wire
Voltage range +10%/-15%
Frequency range  45–65 Hz
Power factor  0.99 (minimum)
Input current distortion  <3% (no input filter required)
Soft-start capability Yes
   
Output characteristics  
Voltage  480V 3Wire
Regulation  ±1%
Inverter  PWM with IGBT switching
Voltage THD <1% (100% linear load); <5% (non-linear load)
Load power factor range  Up to a 0.7 power factor lagging to 0.9 power factor leading without derating
Overload 110% for 10 minutes, 125% for 2 minutes, 150% for 15 seconds
   
Battery  
Battery types  VRLA, AGM, wet cell, lithium-ion
Battery voltage  480V
Temperature compensation  Optional
Charging method  ABM technology or float, selectable
   
Dimensions and weights  
1000 kW/1000 kVA 147”w x 34.3”d x 77.3”h (5,295 lb/2,402 Kg)
1000 kW/1100 kVA 147”w x 34.3”d x 77.3”h (5,295 lb/2,402 Kg)
1100 kW/1100 kVA 147”w x 34.3”d x 77.3”h (5,295 lb/2,402 Kg)
   
Options
  • External maintenance bypass
  • PDU, RPP and STS
  • Maintenance bypass module, matching cabinet, 2/3/4 breaker
  • DC disconnects
  • 100 kAIC input breakers
   
Communication cards

Four communication bays as standard. The following connectivity options can be installed at any time:

 

Remote inputs/outputs: Five building alarm inputs and one summary alarm contact (5A @ 120V) as standard

Remote monitor panel: Eight backlit status indicator lamps plus an audible horn

   
Software compatibility

Eaton Intelligence Platform:

  • Automate: make tasks simpler via advanced alerts and automated resolution
  • Monitor: make data actionable through faster, scalable interpretation and analysis
  • Visualise: see beyond power consumption through 3D infrastructure visualisations
  • Predict: foresee power component failure with cloud-based analytics
Note: Due to continuous improvement, specifications are subject to change without notice. Please refer to Eaton Power Xpert 9395 technical documents for specific configuration guidelines and features.