Download document () of 20
Pow-R-Command lighting control

Pow-R-Command 2000E main panelboard

Pow-R-Command PRC2000E main panelboard provides web-enabled lighting control and plug load control system. Intended for applications requiring switching and dimming control. Preconfigured web pages allow local and remote programming, monitoring and override control using a standard web browser or mobile device. Onboard Bacnet/IP, Modbus TCP and Modbus RTU protocols allow integrating directly with building management systems. Email notification notifies personnel of system alarm conditions.   

Code compliant
ASHRAE, IECC and California Title 24 standards
Integrated design
Branch-circuit protection and lighting control
Leading technology
Web-enabled and responsive design

Core features

  • Networked or standalone operation
  • ARM9 32-bit RISC CPU, Linux operating system
  • No on-board battery, RoHS compliant
  • Cost-effective lighting and energy management system with flexible main/expansion panelboards architecture
  • Integrated cybersecurity features, including GSA certification
  • Controller commonly used in panelboards and switchboards 

Designed to meet mandated energy codes

 
Meets ASHRAE, IECC and California Title 24 standards for network lighting control systems
 
 
Lighted space - feature block

Learn more about our Pow-R-Line Xpert line of panelboards and switchboards

You may also be interested in

Questions?

Email

Email
lightingcontrol@eaton.com

Phone Phone
+1-833-POW-R-CMD (769-7263)
Specifications

Features

ETHERNET COMMUNICATION

Utilizes existing building Ethernet infrastructure providing network communication and remote access via computers or mobile devices

EMBEDDED WEB SERVER

Embedded web server eliminates the need for custom software; integrated HTML5 webpages allow programming and monitoring using any web browser

FRONT ETHERNET MAINTENANCE PORT

Easy local PC connection access to all controller functions

FRONT COLOR LCD TOUCHSCREEN

Easy local access to limited controller functions

PRCE EXPANSION PANELBOARDS SCALEBILITY (SLAN)

Supports up to eight Breaker Control Bus (BCB) controllers on integrated TIA-485 Sub-LAN network (SLAN); up to 168 remotely-operated breakers are supported

DIGITAL INPUTS

Eight dry-contact digital inputs and eight universal inputs (shared with analog inputs) for connection of motion detectors or other On/Off devices

ANALOG INPUTS

Eight 0-10 Vdc analog inputs for connecting indoor, outdoor, atrium, and skylight photosensors

ANALOG OUTPUTS

Eight 0-10 Vdc analog outputs for connecting LED dimming drivers and fluorescent dimming ballasts

APPLICATION SPECIFIC MODULES NETWORK (MLAN)

Connect up to 15 AEMs, DEMs, or Energy Meters to the  controller over the TIA-485 network

DIGITAL EXPANSION MODULE (DEM)

Each optional DEM provides eight maintained dry contact inputs for connecting motion detectors or other On/Off devices and eight digital outputs for optional status indicators

ANALOG EXPANSION MODULE (AEM)

Each optional AEM provides eight 0-10 Vdc analog inputs for connecting indoor, outdoor, atrium, and skylight photosensors , and eight analog 0-10 Vdc analog outputs for connecting LED dimming drivers and fluorescent dimming ballasts

ENERGY METERS

Connection for up to 15 energy meters on the MLAN network (shared with AEMs and DEMs) and provides pass-through meter data mode to the Ethernet port

DIGITAL SWITCH NETWORK (DSN)

Connection for up to 99 Digital Switches capable of On/Off and dimming functionality in the local areas

TIA-485 COMMUNICATION

TIA-485 communication port supporting backward compatibility with legacy PRC controllers

TIME SCHEDULE BASED LOGIC

250 time schedules available for local control; each time schedule is capable of up to five occupant warning winks

GROUP LOGIC

250 groups to logically connect multiple breakers for single command control

AUTOMATIC DAYLIGHT HARVESTING AND DIMMING

Fully integrated dimming algorithms with analog I/O available for photosensors and dimming drivers

ADVANCED LOGIC PROGRAMMING

Capabilities for advanced controls, monitors, and other logic programming and a  full global objects sharing between the PRCE controllers

EMAIL MESSAGING

Fully configurable email notifications providing notifications on events, alarms, messages, etc.

ETHERNET TIME SYNCHRONIZATION

Allows connection to local NTP servers to automatically adjust the time in the controller (where available)

BUILDING AUTOMATION SYSTEMS

BACnet/IP, Modbus TCP, and Modbus RTU servers for integration to the BAS systems

PRC5000E BUILDING CONTROLLER

Recommended for medium and large lighting control systems

Global system schedules

Lighting controls network management tools

Custom graphics viewed using web browser

Lighting panelboard configurations

REMOTE-OPERATED CIRCUIT BREAKERS

120/240 V system

Single pole 15-, 20- and 30 A

Two pole 15-, 20-, 30-, 40- and 50 A

 

480/277 V system

Single pole 15-, 20- and 30 A

Two pole 15-, 20-, 30 A

STANDARD CONFIGURATIONS

Pow-R-Line 1a for maximum of 240 Vac systems

Pow-R-Line 2a for maximum of 480 Vac systems 

Integrated Facility System (IFS)

Questions?

Email

Email
lightingcontrol@eaton.com

Phone Phone
+1-833-POW-R-CMD (769-7263)
Download Links

Questions?

Email

Email
lightingcontrol@eaton.com

Phone Phone
+1-833-POW-R-CMD (769-7263)