1200VA 600W Line-Interactive UPS with 8 Outlets - AVR, 120V, 50/60 Hz, LCD, USB, Tower
Product Name |
Eaton Tripp Lite series UPS
|
Catalog Number |
OMNIVS1200LCD
|
UPC |
037332214089
|
Product Length/Depth |
19.5 in
|
Product Height |
11.7 in
|
Product Width |
9.3 in
|
Product Weight |
19.2 lb
|
Compliances |
FCC Class A
RoHS |
Certifications |
NOM
CSA certified UL 1778 RETIE |
Topology |
Line-interactive
|
Form factor |
Desktop
|
Package contents |
|
Input nominal voltage |
120 VAC
|
Nominal frequency |
50/60 Hz
|
Input frequency range |
50/60 Hz
|
Receptacle |
5-15R
|
Output nominal voltage |
110 / 120V
|
Electric current - max |
|
Runtime at half load |
12 min
|
Relative humidity |
0-90% non-condensing
|
Front Panel LCD Display |
Touchscreen LCD reports input voltage, output voltage, load percentage, battery charge percentage and overload status
|
Output Receptacles |
5-15R
|
Product Highlights |
Easy-to-read LCD touchscreen gives valuable voltage, load and battery data
Protects equipment against blackouts, brownouts, overvoltages, surges and line noise Battery backup supplies power during outages; AVR corrects low and high voltages 8 NEMA 5-15R outlets provide power to PC, home theater and digital signage equipment High >95% efficiency with low BTU ratings saves power and lowers energy costs High >95% efficiency with low BTU ratings saves power and lowers energy costs |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
|
Nominal Output Voltage |
110V
115V 120V |
Network Management Cards Details |
Network management not supported
|
Output power factor |
0.5
|
Phase (input) |
Single-phase
|
Runtime at full load |
2 min. (600W)
|
Communication interface |
USB (HID enabled)
USB interface cable included |
Battery Access |
Battery access door
|
Dc Voltage |
12
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB interface cable included
|
Input Circuit Breakers |
15A
|
High Voltage Transfer to Battery Power |
145
|
Low Voltage Transfer to Battery Power |
89
|
Undervoltage Correction |
Input voltages between 89 and 108 are boosted by 18%
|
Application |
|
Switch configuration |
Power off/on switch
|
Hot Swap PDU Options |
PDUB15 (2U / 8 5-15R outlets)
|
AC suppression joule rating |
316
|
Housing material |
ABS
|
Output AC waveform (AC mode) |
Pure sine wave
|
Output AC waveform (battery mode) |
PWM sine wave
|
Output Capacity (kVA) |
1.2
|
Output Capacity (kW) |
.6
|
Output Capacity (VA) |
1200
|
Output Capacity Details |
10A @ 120V. (LINE MODE) 110%±10%,GOES TO FAULT AFTER 5MIN; 120%±10%,GOES TO FAULT IMMEDIATELY; (BATTERY MODE) 110%±10%,SHUTS DOWN IN 5 SEC; 120%±10%, SHUTS DOWN IMMEDIATELY
|
Primary UPS Depth (mm) |
381
|
Primary UPS Height (mm) |
191
|
Primary UPS Width (mm) |
140
|
AC Suppression Response Time |
Instantaneous
|
Audible Alarms |
UPS remains silent in battery backup mode; Alarm sounds only to report low-battery, fault, overload and replace-battery conditions
|
Battery Start Capability |
Cold-start operation supported
|
Battery Replacement Description |
Replaceable internal batteries (see manual)
|
Frequency Rating Details |
Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal.
|
Output Voltage Regulation (Line Mode) |
120V (+6%/-12%)
|
Output Voltage Regulation(Battery Mode) |
120V (±10%)
|
Overvoltage Correction |
Input voltages between 128 and 149 are reduced by 15%
|
Rechargeable Battery |
8 hours (10% to 90%)
|
Recommended Electrical Service |
15A 120V
|
Storage Temperature |
5° to 113°F (-15° to 45°C )
|
Nominal Voltage Details |
120V sinusoidal in line mode and 120V PWM in battery mode
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 89 to 145
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
Maximum Input Amps |
12
|
UPS Input Cord Length (m) |
1.5
|
UPS Power Module Dimensions |
7.5 x 5.5 x 15
|
Power Mode Transfer Time |
6 milliseconds typical (10 milliseconds max)
|
Connected Equipment Insurance |
$200,000 Ultimate Lifetime Insurance
|
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
5-15P
|
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS
|
UPS Dataline Suppression |
1 line TEL/DSL or Ethernet
|
UPS Output Receptacles |
6 UPS outlets, 2 surge-only outlets
|
High Availability UPS Features |
Automatic voltage regulation (AVR)
Surge/noise protection |
Support from Eaton