Eaton’s Power Xpert Protection Manager (PXPM) provides a clean, intuitive user interface, enabling unmatched control, testing and troubleshooting. The software is free to download and can run on any PC.
Settings and tests are communicated to trip units via USB or through connected networks, no special test equipment is required.
Troubleshooting is greatly simplified, using historical event summaries and real-time data provided by the Power Xpert Release (PXR) trip units and saving the customer time and money.
PXPM installation requires the user to have administrative privileges on the PC. Privileges may be gained by right clicking on the installer and selecting “Run as administrator” or escalating to local IT for access.
Eaton’s Power Xpert Protection Manager (PXPM) provides a clean, intuitive user interface, enabling unmatched control, testing and troubleshooting. The software is free to download and can run on any PC. This training video covers features of the PXPM, including configuration and reporting as well as the reading and capturing of real-time data. The training also includes instruction on and demonstration of licence features, such as secondary injection testing and waveform capture.
To navigate quickly though the training, please use the Chapters button (available in the bottom right-hand corner of the menu bar) to navigate directly to a chapter.
Power Defense or NZM moulded case circuit breaker |
Power Defense or IZMX |
|||||
---|---|---|---|---|---|---|
Feature |
PXR 10 |
PXR 20 |
PXR 20D |
PXR 25 |
PXR 20/25 |
|
Setpoint configuration | Read | X | X | X | X | X |
Write | X * | X * | X | X | X * | |
Modify trip unit settings | Resetting – diagnostics and data ^ |
X | X | X | LED, diagnostics, data | |
Real-time clock | X | X | X | X | ||
Change trip unit display language | X | X | X | |||
Test mode | Open circuit breaker test | X | X | X | X | X |
Advanced testing – functional (licensed) | X Trip-only |
X | X | X | X | |
Advanced testing – sensor continuity (licensed) | X | X | X | X | X | |
View breaker information | X | X | X | X | X | |
Real-time data | X | X | X | X | X | |
Event summaries | Trip event details | 1 | 10 | 10 | 10 | 10 |
Alarm event details | 0 | 10 | 10 | 10 | 10 | |
Total available events | 200* | 200* | 200* | 200* | ||
Real-time clock | X | X | X | X | ||
Trip/alarm event waveform (licensed) | X | X | X | X |
Licences are PC-specific. Be sure to download the LicReq file from the PC you want to license.
From the PXPM software interface, select
Application settings > Licence.
Select the Request licence button next to the feature that you would like to license.
Visit Eaton.mybigcommerce.com/power-xpert-protection-manager/.
You will be prompted to attach your licence request (.LicReq) file from step 2 before adding the item to your basket.
You will receive your licence files as an email attachment from PXPMLicense@eaton.com. (Save or archive this email in the event that a reinstallation is needed.)
Save these to your PC.
Click on Install licence and select the licence (.License) file you received in step 4. If the licence was installed correctly, a tick will appear next to the licence.
The number of remaining sessions will be displayed on the licence screen.